Input Voltage
|
115 or 230VAC, 48…410Hz +/-2 are standard
Other inputs available, please consult factory
|
Input Protection
|
Termal fuse, Inrush current limiting, Reverse polarity protection
|
Isolation
|
2250 VDC input to chassis / 2250 VDC input to output / 2250 VDC output to chassis
|
Output Voltage
|
115VAC / 60Hz / 17.3A or 115VAC / 400Hz / 17.3A or
230VAC / 50Hz / 8.6A continuous with grounded neutral
Isolated ?oating output optional (Consult factory for other voltages and frequencies)
|
Wave Form
|
Sinusoidal
|
Total Harmonic Distortion
|
Less than 5% at full load
|
Efciency
|
Min 78% at full load
|
Line Regulation
|
Maximum 0.5%
|
Load Regulation
|
Maximum ± 6% from 1 load to full load
|
Output Protection
|
Current limiting with short circuit protection, thermal shutdown with automatic recovery in case of continuous overload or insufcient air?ow
|
EMI
|
Meets EN 55022 Class B
|
Load Crest Factor
|
Maximum 3.0 at 9 load
|
Operating Temperature Range
|
0o C to +50o C
Extended range available (Consult factory)
|
Humidity
|
5 - 95% non-condensing
|
Temperature Drif
|
0.05% per o C over operating temperature range
|
Dimensions
|
3U” X 19” x 15”
(H x L x W) enclosed case
|
Connections
|
Input: Compression-type terminal
Output: Standard AC receptacle
|
Weight
|
40 pounds (18.2 Kg)
|
Safety
|
Compliance to IEC950, CSA C22.2 No. 950 and UL 1950
Please contact factory for approval status for the requested input/output confguration
|